R422D refrigerant gas cylinder supplied by SLIHE CHEMICAL

R422D Refrigerant Gas

HFC blend · R-422D ASHRAE A1 ODP 0 GWP 2,729 Purity ≥99.9%

R422D exists for one job: getting an R22 system off R22 without draining and flushing the oil. The 3.4% of R600a raises oil solubility enough that most mineral-oil and alkylbenzene systems can keep their charge, and the 65.1% R125 share keeps pressures close to R22. The trade-off is GWP: at 2,729 it is higher than the R22 it replaces.

Physical properties

Chemical nameR-422D
CompositionR-125 65.1 / R-134a 31.5 / R-600a 3.4 (% mass)
Molecular formulaR-125 / R-134a / R-600a
Molecular weight131.0
Boiling point 101.3KPa(℃)-43.2
Freezing point 101.3KPa(℃)-95.0
Liquid density 30℃(kg/㎥)1,130
Critical temperature(℃)81.7
Critical pressure(MPa)4.03
ODP0
GWP2,729 (AR4) / 2,473 (AR5)

Quality index

Purity≥99.9%
Water content≤0.001%
Acidity≤0.00001%
Evaporation residue≤0.01%
Chloride content-
Appearancecolorless and clear
Odorodorless

Applications

R22 retrofits in direct-expansion comfort cooling, packaged rooftop units, medium-temperature walk-in coolers and process chillers where a full oil change is impractical. Not intended for flooded evaporators or systems with large refrigerant receivers.

Packing options

  • Can: -
  • Disposable cylinder: 13.6kg(30Lbs) / 22.7kg(50Lbs)
  • Refillable cylinder: 50kg / 100kg / 800kg
  • ISO-TANK: 926L / 20ft ISO

Advantages & limitations

  • Retains the existing mineral oil or alkylbenzene in most systems, avoiding a flush and two oil changes
  • Pressure envelope close to R22, so the compressor and relief settings stay valid
  • ASHRAE A1 non-flammable and zero ODP
  • A practical route for older equipment where the owner will not fund a full conversion
  • GWP 2,729 is higher than R22 at 1,810, so it is a compliance step sideways rather than forward
  • Capacity drops 5-15% against R22 depending on evaporating temperature
  • Glide around 4-5 K requires liquid charging and TXV adjustment
  • Excluded from most new-equipment categories by 2025 EU and US rules

Replacements

Replaces: R22 in mineral-oil and alkylbenzene systems where the oil charge cannot be replaced

Replaced by: R438A or R407C where a fuller conversion is possible, and R454C/R455A in new A2L equipment

Regulations & phase-out

R422D is a transitional product and the regulations treat it that way. It is an HFC, so it consumes quota at 2,729 CO₂ equivalent per kilogramme, and because that figure exceeds R22's own 1,810 it offers no climate benefit over the gas it replaces. Buyers use it to buy time on equipment that will be replaced rather than retrofitted again.

  • 2010EU bans virgin HCFC for new equipment; R422D enters the market as an R22 retrofit for mineral-oil systems.
  • 2015EU Regulation 517/2014 caps the HFC quota and begins the step-down that raises R422D cost each year.
  • 2020US EPA SNAP delists R422D for new cold storage warehouses, keeping it for retrofit and service only.
  • 2025US Technology Transitions rule limits new stationary refrigeration to GWP 150, and EU quota falls to 63% of baseline.

Sources: Regulation (EU) 517/2014 and 2024/573; US EPA SNAP and Technology Transitions rules; IPCC AR4/AR5 GWP100 values.