R407F refrigerant gas cylinder supplied by SLIHE CHEMICAL

R407F Refrigerant Gas

HFC blend · R-407F ASHRAE A1 ODP 0 GWP 1,824 Purity ≥99.9%

R407F moves the same 20/40/40 idea one step further: by lifting R32 to 30% and R134a to 40% it drops GWP to 1,824, 53% below R404A, while keeping a boiling point of -46.06 °C within a whisker of R404A's -46.2 °C. In supermarket medium-temperature racks that translates into slightly lower discharge temperatures and a measurable efficiency gain over R407A.

Physical properties

Chemical nameR-407F
CompositionR-32 30 / R-125 30 / R-134a 40 (% mass, zeotropic)
Molecular formulaR-32 / R-125 / R-134a
Molecular weight82.06
Boiling point 101.3KPa(℃)-46.06
Freezing point 101.3KPa(℃)-95.0
Liquid density 30℃(kg/㎥)1,040
Critical temperature(℃)82.66
Critical pressure(MPa)4.755
ODP0
GWP1,824 (AR4) / 1,674 (AR5)

Quality index

Purity≥99.9%
Water content≤0.001%
Acidity≤0.00001%
Evaporation residue≤0.01%
Chloride content-
Appearancecolorless and clear
Odorodorless

Applications

Supermarket medium-temperature racks, dairy and produce cases, cold storage at -5 °C to -25 °C, and R404A retrofits where the owner wants a lower quota charge without moving to an A2L fluid. Also used in R22 systems after a full POE conversion where capacity must not drop.

Packing options

  • Can: -
  • Disposable cylinder: 13.6kg(30Lbs) / 22.7kg(50Lbs)
  • Refillable cylinder: 50kg / 100kg / 400kg / 800kg
  • ISO-TANK: 926L / 20ft ISO

Advantages & limitations

  • GWP 1,824 is 53% below R404A and 13% below R407A on the same duty
  • Boiling point -46.06 °C matches R404A closely, so evaporator performance is preserved
  • Lower discharge temperature than R404A extends compressor life in hot climates
  • ASHRAE A1 and fully miscible with POE, so no oil chemistry change on a converted system
  • Glide around 6.0-6.4 K, higher than R407A: liquid charging and TXV re-trim are mandatory
  • Higher R32 content means higher discharge pressure than R407A at the same condensing temperature
  • GWP above the 150 and 750 thresholds now applied to new equipment in Europe and the US
  • Cost per kilogramme sits above R407A because of the R32 share

Replacements

Replaces: R404A, R507A and R22 (after POE conversion) in medium-temperature commercial refrigeration

Replaced by: R448A or R449A where GWP must fall further, or R454C/R455A in new A2L equipment

Regulations & phase-out

R407F was designed for the decade between the R404A service ban and the arrival of A2L equipment, and that is exactly where it now sits. It is legal to use for service and for retrofit across the EU and the US, but it does not clear the GWP thresholds applied to new supermarket systems, so its market is maintenance and conversion rather than new build.

  • 2014Honeywell launches Genetron Performax LT (R407F) as an R404A retrofit with a lower GWP and better efficiency.
  • 2015EU F-gas Regulation 517/2014 bans R404A in new equipment, opening the retrofit market for R407F.
  • 2020EU virgin R404A service ban above 2,500 GWP accelerates conversion of existing racks to R407F and R448A.
  • 2023US EPA proposes GWP limits for new supermarket systems under the Technology Transitions rule, excluding R407F from new installs.
  • 2025EU Regulation 2024/573 quota step-down raises the cost of every kilogramme of R407F by roughly a fifth against 2024.

Sources: Honeywell Genetron Performax LT technical data; Regulation (EU) 517/2014 and 2024/573; US EPA, Technology Transitions rule; IPCC AR4/AR5.