R143a refrigerant gas cylinder supplied by SLIHE CHEMICAL

R143a Refrigerant Gas

HFC · HFC-143a ASHRAE A2L ODP 0 GWP 4,470 Purity ≥99.5%

R143a is the refrigeration-grade HFC that gives R404A and R507A their bite at low temperature. Its boiling point of -47.2 °C sits close to R22, but its volumetric capacity is higher, which is why blenders pair it with R125 rather than using it alone. We supply it at 99.5% with the trace moisture and acidity limits blend plants need to keep a formulation stable.

Physical properties

Chemical nameHFC-143a
CompositionSingle component (HFC-143a, 1,1,1-trifluoroethane)
Molecular formulaCH3CF3
Molecular weight84.04
Boiling point 101.3KPa(℃)-47.2
Freezing point 101.3KPa(℃)-117.0
Liquid density 30℃(kg/㎥)905
Critical temperature(℃)73.15
Critical pressure(MPa)3.76
ODP0
GWP4,470 (AR4) / 4,800 (AR5)

Quality index

Purity≥99.5%
Water content≤0.001%
Acidity≤0.00001%
Evaporation residue≤0.01%
Chloride content-
Appearancecolorless and clear
Odorodorless

Applications

Blend component for R404A (52%) and R507A (50%); single-fluid low-temperature freezing and blast freezers where a compact compressor is preferred; component of R427A; also used as a chemical intermediate and in specialty solvent applications.

Packing options

  • Can: -
  • Disposable cylinder: 9kg
  • Refillable cylinder: 926L
  • ISO-TANK: 20ft ISO on request

Advantages & limitations

  • Volumetric capacity higher than R22 at the same displacement, which suits compact freezing compressors
  • Boiling point -47.2 °C is close enough to R22 for a like-for-like evaporator design
  • Zero ODP and good stability with POE lubricants
  • Bulk 926L and ISO supply lets blend plants keep composition within tight tolerances
  • ASHRAE A2L: mildly flammable, so charge limits and ignition-source assessment apply
  • GWP 4,470 (AR4): one of the highest of any HFC still in trade
  • Rarely sold as a stand-alone refrigerant, so availability follows blend demand
  • Higher discharge temperature than R22 in high compression ratio duty

Replacements

Replaces: R502 as a blend component, and R22 in low-temperature freezing where capacity matters more than glide

Replaced by: R452A, R448A or R449A in retrofits, and R454C/R455A where an A2L low-GWP blend is acceptable

Regulations & phase-out

R143a carries two regulatory burdens at once: it is an HFC under the quota system, and it is classified A2L, so a system charged with it also has to satisfy flammable-refrigerant installation standards. Most of the volume now moves to blend plants rather than to end users, and those plants price it against the quota, not against R22.

  • 2016Kigali Amendment counts HFC-143a at 4,470-4,800 CO₂ equivalent per kilogramme in the phase-down baseline.
  • 2018ASHRAE Standard 34 reclassifies R143a from A2 to A2L, aligning charge limits with IEC 60335-2-40.
  • 2021China allocates HFC production quotas; R143a output is capped and reported quarterly.
  • 2024EU Regulation 2024/573 and EPA rules push new low-temperature equipment towards GWP below 150, eroding the R404A and R507A base.

Sources: UNEP, Kigali Amendment; ASHRAE Standard 34; IEC 60335-2-40; Regulation (EU) 2024/573; China MEE, HFC quota notices.