R1234ze(E) refrigerant gas cylinder supplied by SLIHE CHEMICAL

R1234ze(E) Refrigerant Gas

HFO · HFO-1234ze(E) ASHRAE A2L ODP 0 GWP <1 Purity ≥99.5%

R1234ze(E) is the HFO that made low-GWP centrifugal chillers possible. Its critical temperature of 109.4 °C sits far above R134a's 101 °C, so a chiller designed around it condenses comfortably in hot climates, and its GWP is below 1 on AR5. It is mildly flammable (A2L), which is the price paid for a molecule that breaks down in the atmosphere within weeks rather than decades.

Physical properties

Chemical nameHFO-1234ze(E)
CompositionSingle component (trans-1,3,3,3-tetrafluoropropene)
Molecular formulaCF3CH=CHF
Molecular weight114.04
Boiling point 101.3KPa(℃)-19.0
Freezing point 101.3KPa(℃)-156.0
Liquid density 30℃(kg/㎥)1,270
Critical temperature(℃)109.4
Critical pressure(MPa)3.64
ODP0
GWP<1 (AR5) / 6 (AR4)

Quality index

Purity≥99.5%
Water content≤0.001%
Acidity≤0.00001%
Evaporation residue≤0.01%
Chloride content-
Appearancecolorless and clear
Odorodorless

Applications

Centrifugal and screw chillers for commercial buildings, high-temperature heat pumps up to 90 °C delivery, medium-temperature refrigeration, ORC power cycles, and as the HFO component of blends such as R513A, R515B and R454C. Also used as a foam blowing agent for XPS and PU panels.

Packing options

  • Can: -
  • Disposable cylinder: 13.6kg(30Lbs) A2L-rated
  • Refillable cylinder: 50kg / 100kg / 400kg
  • ISO-TANK: 926L / 20ft ISO

Advantages & limitations

  • GWP below 1 on AR5: effectively outside the HFC quota system in both Europe and the US
  • Critical temperature 109.4 °C allows air-cooled chillers to condense at 45-50 °C ambient
  • Zero glide as a single component, so no fractionation and no liquid-charging complication
  • Miscible with POE and approved by the major chiller OEMs for new equipment
  • ASHRAE A2L mildly flammable: charge limits, leak detection and ignition-source control apply
  • Volumetric capacity about 20% lower than R134a, so the compressor must be sized for it
  • Not a drop-in for an existing R134a chiller without an OEM-approved conversion package
  • Supplied as a liquefied gas, so dedicated A2L-rated cylinders and fittings are required

Replacements

Replaces: R134a in new centrifugal and screw chillers, and R134a as a foam blowing agent

Replaced by: No lower-GWP drop-in; R1234ze(E) is itself the destination fluid for new chiller designs

Regulations & phase-out

R1234ze(E) is what the regulations were written to encourage. Its AR5 GWP below 1 clears every threshold in the EU F-gas Regulation and the US EPA Technology Transitions rule, and its short atmospheric lifetime means it is not counted in the HFC quota at all. The remaining constraint is safety, not climate: A2L charge limits under IEC 60335-2-40 govern how much can go into a given plant room.

  • 2011Honeywell commercialises Solstice ze (R1234ze(E)) for chillers and foam blowing.
  • 2014EU F-gas Regulation 517/2014 recognises HFOs as the route to GWP below 150 for new chillers.
  • 2018ASHRAE Standard 34 confirms the A2L classification; IEC 60335-2-40 sets the charge limits used in plant-room design.
  • 2022China adds HFO-1234ze to its controlled-substance list with reporting but no phase-down obligation.
  • 2025US EPA Technology Transitions rule and EU 2024/573 both make R1234ze(E) the default for new commercial chillers.

Sources: Honeywell Solstice ze technical data sheet; Regulation (EU) 2024/573; US EPA, Technology Transitions rule (40 CFR 84); ASHRAE Standard 34; IEC 60335-2-40.

Need R1234ze(E) price and MOQ?

Tell us your destination port and quantity — we reply within 12 hours.