Published 2026-11-10 · SLIHE technical guide · Retrofit blends and CO₂ compared

R404A has been the default refrigerant for commercial refrigeration for a quarter of a century — and it is now the most tightly regulated gas on the books. Anyone operating supermarket racks, cold rooms or refrigerated transport is already living with the consequences, and sooner or later every one of those systems will need a decision about what comes next. This guide compares the four practical paths: the retrofit blends R448A, R449A and R452A, and the natural alternative CO₂ (R744), and shows where each one fits.

Why R404A has to go

Three forces are converging on R404A at the same time:

  • Climate impact. At GWP 3,943 (IPCC AR5), one kilogram of R404A released to the atmosphere equals about 3.9 tonnes of CO₂ — among the highest values of any refrigerant still in common use. R404A sits at the very top of the global phase-down curve.
  • Regulation. The EU has barred virgin refrigerant with GWP 2,500 or above from servicing equipment since 2020, and reclaimed R404A may be used only until 2030. Regulation (EU) 2024/573 continues the HFC quota phase-down towards zero by 2050. In the United States, EPA's Technology Transitions rule has prohibited R404A-class blends in new refrigerated road, marine and intermodal systems since 1 January 2025, and caps most new stationary refrigeration at GWP 150 from 2026–2027.
  • Cost. Quota cuts restrict supply while cold-chain demand keeps growing. Our October 2026 price report recorded R404A at 4,913 USD/ton FOB China, up 1.3% on the month — and every future quota step makes the arithmetic harder.

The phase-down arithmetic deserves a closer look, because it drives the business case. Quotas are measured in CO₂-equivalent tonnes, so each kilogram of R448A or R449A charged counts against your supplier's allowance at roughly one third of the weight of a kilogram of R404A. Converting a fleet from R404A therefore frees quota, stabilises supply, and cuts direct emissions by two thirds in one step.

R448A: the all-round match for medium-temperature racks

R448A mixes R32, R125, R1234ze(E), R1234yf and R134a (26/26/20/21/7 wt.%) into a non-flammable A1 blend with a GWP of 1,273 (AR5) — 68% below R404A. In medium-temperature supermarket racks its cooling capacity lands within a few percent of R404A, and field conversions routinely report equal or better energy performance, especially in warm climates where higher condensing temperatures punish inefficient blends hardest. Because it sits far below the EU's 2,500 service threshold, a rack converted today can still be topped up with virgin gas for many years — a sharp contrast with R404A's reclaimed-only future.

The trade-offs: R448A is zeotropic, with a temperature glide of roughly 4.6 K, so systems must be charged as liquid and expansion valves re-tuned after conversion. In deep-freeze duty its capacity falls away noticeably — that is what the next two candidates are for.

R449A: the retrofit workhorse

R449A combines R32, R125, R134a and R1234yf (24.3/24.7/25.7/25.3 wt.%) at GWP 1,282 (AR5), a 67% cut from R404A. Its composition was tuned to track R404A capacity and efficiency across both medium- and low-temperature applications, which is why several transport-refrigeration manufacturers adopted it early for trailer and truck units. For contractors who want one blend to cover a mixed portfolio of racks, cold rooms and transport units, R449A is usually the simplest answer. Glide is close to R448A's at about 4.7 K, so the retrofit routine is identical: liquid charging, new filter drier, valve adjustment.

R452A: built for deep freeze and transport

R452A blends R32, R125 and R1234yf (11/59/30 wt.%) at GWP 2,141 (AR5) — a 46% cut. The deliberately high R125 share is the point: it keeps cooling capacity up and discharge temperature manageable in low-temperature operation, exactly the duty range where R448A and R449A lose output. Deep-freeze cold rooms, blast freezers and refrigerated transport are its home ground, and like the other two it stays below the 2,500 service threshold, so converted equipment keeps virgin-gas serviceability. The price of that capability is quota weight and cost: every kilogram of R452A counts nearly twice as heavy as R448A against the phase-down, and its price per tonne sits higher.

CO₂ (R744): the endgame option for new equipment

R744 is carbon dioxide: GWP 1, non-flammable, non-toxic (ASHRAE A1), cheap and available in every country on earth. No phase-down rule will ever restrict it. That combination is why European supermarket chains now standardise on transcritical CO₂ systems for new stores, and why it is the only option in this guide that is genuinely future-proof.

The ambition has a price. CO₂ works above its critical point of 31.1 °C and 73.8 bar, so transcritical racks run their gas coolers at up to 120 bar — every compressor, valve and safety device is specific to R744, and technicians need dedicated training. It is a new-system refrigerant, not a retrofit: pressures and components are simply incompatible with an R404A rack. Efficiency is excellent in cool climates; in hot regions, parallel compression and ejectors recover most of the gap. A popular middle path is the cascade system — CO₂ on the low stage paired with propane (R290) or a low-GWP HFC on the high stage — which keeps pressures moderate and efficiency high year-round.

Side-by-side comparison

R404AR448AR449AR452AR744 (CO₂)
GWP (IPCC AR5)3,9431,2731,2822,1411
ASHRAE safety classA1A1A1A1A1
Composition (wt.%)R125/R143a/R134a 44/52/4R32/R125/R1234ze(E)/R1234yf/R134a 26/26/20/21/7R32/R125/R134a/R1234yf 24.3/24.7/25.7/25.3R32/R125/R1234yf 11/59/30pure substance
Capacity, medium tempbaselinewithin a few %within a few %closenew system
Capacity, low tempbaselinereducedcloseclosenew system
Temperature glidesmall≈ 4.6 K≈ 4.7 K≈ 4.7 Knone
Retrofit onto R404A system—yesyesyesno
Best fitlegacy service onlyMT supermarket racksMT + LT mixed portfoliosLT cold rooms, transportnew builds, cool climates

Retrofit checklist: R404A to an A1 HFO blend

The conversion itself is straightforward for a trained crew — usually one working day for a typical rack or transport unit. What separates a clean conversion from a troublesome one is discipline in the details:

  1. Size the charge. R448A, R449A and R452A all run close to the R404A charge weight; follow the blend maker's conversion table rather than guessing.
  2. Check the oil. Most R404A systems already run on POE oil — verify viscosity against the blend maker's spec and replace it only if the audit says so. Alkylbenzene oil must be fully converted to POE.
  3. Fit a new filter drier. Non-negotiable on every conversion.
  4. Recover completely, then charge liquid. Never top R404A up with a retrofit blend or mix leftovers. Because the blends are zeotropic, always charge through the liquid line so every component enters in the right proportion.
  5. Re-tune the controls. Adjust or resize expansion valves, check superheat, and review high-pressure and discharge-temperature protection — especially on low-temperature systems.
  6. Relabel and record. Update the equipment nameplate with the new blend, charge weight and oil, and file the conversion report. Leak-inspection rules and refrigerant logbooks both refer to the label.
  7. Verify performance. Log capacity, energy use and discharge temperature over the first weeks. If a deep-freeze system loses capacity on R448A or R449A, R452A is the fix.

Which replacement fits your application?

ApplicationFirst choiceAlso works
Supermarket racks, medium temperatureR448AR449A
Cold rooms and deep-freeze storesR452AR449A; CO₂ cascade for new builds
Refrigerated trucks, trailers and containersR452AR449A
New supermarket or warehouseCO₂ transcriticalCO₂/R290 cascade; R449A or R448A as transition

Questions buyers ask

Can I top up R404A with a retrofit blend?

No. R448A, R449A and R452A are not mixing partners for R404A — blending them changes the composition, degrades performance and can leave a system that neither works properly nor complies with the label. Recover the R404A completely, evacuate, and charge the new blend fresh.

Do I need to change the compressor oil?

Usually not. R404A systems were built on POE oil, which the retrofit blends accept. Verify the viscosity grade, have the oil acidity checked on older systems, and replace the filter drier. Mineral or alkylbenzene oils are the exception and must be fully converted to POE.

Why does glide matter when charging?

A zeotropic blend evaporates over a temperature range, so its components can separate if charged as vapour. Charging as liquid keeps the factory composition intact; otherwise the blend in the system drifts away from the specification and capacity drops.

Will capacity drop after converting a deep-freeze system?

On R448A it will, and on R449A it may. That is a known property of the blends, not an installation fault. Where deep-freeze capacity is critical, convert directly to R452A or plan the system for a CO₂ cascade.

Is CO₂ legal everywhere?

Yes — GWP 1 faces no phase-down restriction in any major market. The real constraints are engineering ones: pressure-equipment codes, component availability and technician training, all of which improve every year as CO₂ systems multiply.

Data notes: GWP values follow IPCC AR5. EU rules per Regulation (EU) 2024/573 and its predecessors; US rules per the AIM Act and EPA's Technology Transitions rule. Capacity and efficiency statements reflect OEM retrofit data and field experience; always validate against the compressor and system data before committing a conversion.

Planning a conversion?

Whether you are converting one rack or standardising a fleet, the blend you choose will define service costs for the next decade. SLIHE manufactures R448A, R449A and R452A factory-direct in Zhejiang, China, and ships worldwide in disposable cylinders, refillable drums and ISO tanks, with full export documentation.